Probes and accessories · AC-RHT

Digital temperature and humidity probe

The external digital probe for the Node+ Digital, built around the Sensirion SHT85 element: temperature and relative humidity on one shielded cable.

  • Wired to Node+
  • Temperature
  • Humidity

Probe and cable technical drawings: PDF, 6 pages, 352 KB

Sensor element
Sensirion SHT85
Range
−40 °C to +105 °C; 0 to 100% RH (non-condensing)
Accuracy
±0.1 °C (typical, 20 to 50 °C); ±1.5% RH (typical)
Drawing of the temperature and humidity probe head and cable

Key specifications

Temperature and humidity probe at a glance

Copied from the Probe and cable technical drawings. The full tables are further down.

Key specifications of the Digital temperature and humidity probe
Sensor elementSensirion SHT85
Range−40 °C to +105 °C; 0 to 100% RH (non-condensing)
Accuracy±0.1 °C (typical, 20 to 50 °C); ±1.5% RH (typical)
OutputI²C digital
Cable22 AWG 4-core, FEP insulation, braided shield, black FEP jacket; 100 mm protective sleeve
Cable length1000 ±50 mm
Node connectorHR30-6P-6S
MaterialsRoHS compliant